EasyManua.ls Logo

Toshiba TOSVERT VF-AS1 Series - Page 44

Toshiba TOSVERT VF-AS1 Series
49 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E6581581
- 43 -
Examples of Instance 101/151
Access the inverter parameter is enabled using byte 4 to 6 of this Instance.
Set the communication number of the parameter to byte 4, 5 (Index), and the value to byte 6, 7 (Data).
In case of the monitor parameter “FE**”, the value becomes "communication number - 0x7000 (same as bit14,
15 set to 0)".
Read the parameter cmod (Command mode selection, communication number is 0003).
Instance Byte 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Hex.
5, 4 0 0 00000000000 0 1 1 0x0003
Output Instance 101
7, 6 - - ----------- - - - -
Input Instance 151 5, 4 0 0 00000000000 0 1 1 0x0003
(cmod is set 0.) 7, 6 0 0 00000000000 0 0 0 0x0000
Read the parameter f268 (Initial value of UP/DOWN frequency).
Instance Byte 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Hex.
5, 4 0 0 00001 00110 1 0 0 0 0x0268
Output Instance 101
7, 6 - - ----------- - - - -
Input Instance 151 5, 4 0 0 00001 00110 1 0 0 0 0x0268
(f268 is set 60.0Hz.) 7, 6 0 0 0 1 0 1110 1110 0 0 0 0x1770
Read the parameter fe04 (Voltage of DC bus).
Instance Byte 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Hex.
5, 4 0 0 11111000000 1 0 0 0x3E04
Output Instance 101
7, 6 - - ----------- - - - -
Input Instance 151 5, 4 0 0 11111000000 1 0 0 0x3E04
(fe04 is 94.49%.) 7, 6 0 0 1 001 001110 1 0 0 1 0x24E9
Write “60 (Hz)” to the parameter sr1 (Preset speed 1, communication number is 0018).
Instance Byte 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Hex.
5, 4 1 0 00000000011 0 0 0 0x8018
Output Instance 101
7, 6 0 0 0 1 0 1110 1110 0 0 0 0x1770
5, 4 1 0 00000000011 0 0 0 0x8018
Input Instance 151 (OK)
7, 6 0 0 0 1 0 1110 1110 0 0 0 0x1770
Input Instance 151 (NG) 5, 4 1 1 00000000011 0 0 0 0xC018
(Error code *) 7, 6 0 0 00000000000 0 0 1 0x0001
About byte 0 - 3, refer to section 5.1.3.
* Refer to following about the error code.
1
(00000001):: Data out of range
2
(00000010):: Bad address
3
(00000011):: Read only
4
(00000100):: Stop to modify or permission error
5
(00000101):: All other

Table of Contents

Related product manuals