E658130
- 38 -
6.1. Program example for reading the inverter status
Example 1 shows a ladder logic to read the inverter status.
Y30 of the output unit is turned on when inverter of station 2 is forward running
0 0 0 0 * 0 0 0 0 0 0 0 0 0 0 1
RX0 to RXF
RX10 to RX1F
RX20 to RX2F
RX30 to RX3F
Remote input
Station1
Station 2
Inverter status
b0: Forward running
b1: Reverse running
b2: Output terminal 1
b3: Output terminal 2
b4: Output terminal 3
b5: Failure FL
b6: PI control OFF
b7: Acceleration/deceleration pattern selection (1 or 2)
b8: Emergency stop
b9: Coast stop
b10: Alarm
[Inverter
b15 b8 b7 b0
X0: Module error
X1: Host data link status
X0F: Module ready
SW80.1: Station 2 ready
0 0 0 0 * 0 0 0 0 0 0 0 0 0 0
1
X0
X0F X1
SW80.1
( M0 )
Turn on the relay of output
unit (Y30)
M0
X1020
( Y30 )
[END]
Check the ready of the station 2
Example