6.7. Program example for parameter reading
Example 7 shows a ladder logic to read parameter f311 of station 1 inverter to D2.
f311: Reverse-run prohibition reading code number: 1311H (hexadecimal)
The reply code at the time of instruction code execution is set to D1.
Refer to
5.5.8 for detail.
Check the ready of the station 1
X0
X0F
X1
( M0)
SW80.0
M0
X20
[ PLS M300]
M300
[ SET M301]
M301
X100F
[ MOV H1311 W102]
[ SET Y100F]
[ RST M301]
[ SET M302]
M302
X100F
[ MOV W2 D1]
[ RST Y100F]
[ RST M302]
[ END]
[ MOV W3 D2]
Write f311 read code (1311H)
to
Turn on the instruction code
execution
Read r
everse-run prohibition (RWr3) and
reply code (RWr2) to D2 and D1 when
the instruction code execution
completion
Turn off the instruction code
execution
Example 7

Table of Contents

Other manuals for Toshiba TOSVERT VF-S15 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S15 series and is the answer not in the manual?

Toshiba TOSVERT VF-S15 series Specifications

General IconGeneral
SeriesVF-S15
CategoryInverter
Control MethodV/f control, Sensorless vector control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
Communication OptionsModbus
Braking UnitBuilt-in
Power Rating0.4 kW to 15 kW
Input VoltageSingle-phase 200 to 240V, Three-phase 200 to 240V, 380 to 480V
Cooling MethodFan cooling

Related product manuals