E658130
- 40 -
6.3. Program example for setting the operation commands
Example 3 shows a ladder logic to give a forward command to station 2 inverter.
6.4. Program example for setting the running frequency
Example 4 shows a ladder logic to chang the running frequency of station 1 inverter to
50.00Hz
Set frequency: 5000 (decimal)
X0
X0F
X1
SW80.1
M0
X20
( M0)
(Y1020)
Check the ready of the Station 2
Forward rotation command (RY20)
Example 3
X100D M302
X0
X0F X1
( M0)
SW80.0
M0
X20
[ PLS M300]
M300
[ SET M301]
M301
X100D
[ MOV K5000 W101]
[ SET Y100D]
[ RST Y100D]
[ RST M302]
[ END]
[ RST M301]
[ SET M302]
Check the ready of the station 1
Write set frequency to
Turn off the frequency setting
command RAM (RY0D)
Turn off instruction frequency writing
(RY0D), when instruction frequency
writing completion flag (RX0D) is
turned on.
Example

Table of Contents

Other manuals for Toshiba TOSVERT VF-S15 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S15 series and is the answer not in the manual?

Toshiba TOSVERT VF-S15 series Specifications

General IconGeneral
SeriesVF-S15
CategoryInverter
Control MethodV/f control, Sensorless vector control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
Communication OptionsModbus
Braking UnitBuilt-in
Power Rating0.4 kW to 15 kW
Input VoltageSingle-phase 200 to 240V, Three-phase 200 to 240V, 380 to 480V
Cooling MethodFan cooling

Related product manuals