16
HDWA-SVX001D-EN
Pre-installation
ASHRAE Standard 15
Compliance
Trane recommends that indoor Agility™ chiller
installations fully meet or exceed the guidelines of the
current version of ASHRAE Standard 15, in addition to
any applicable national, state, or local requirements.
This typically includes:
• A refrigerant monitor or detector that is capable of
monitoring and alarming within the acceptable
exposure level of the refrigerant, and that can
actuate mechanical ventilation.
• Audible and visual alarms, activated by the
refrigerant monitor, inside the equipment room and
outside of every entrance.
• The equipment room should be properly vented to
the outdoors, using mechanical ventilation that can
be activated by the refrigerant monitor.
• If required by local or other codes, a self-contained
breathing apparatus should be available in close
proximity to the equipment room.
Refer to the latest copy of ASHRAE Standard 15 for
specific guidelines. Trane assumes no responsibility for
any economic, health, or environmental issues that
may result from an equipment room’s design or
function.
Inspection Checklist
To protect against loss due to damage incurred in
transit, complete the following checklist upon receipt of
the unit.
☐ Inspect the individual pieces of the shipment before
accepting the unit. Check for obvious damage to the
unit or packing material.
☐ Inspect the unit for concealed damage as soon as
possible after delivery and before it is stored.
Concealed damage must be reported within 10 days
after receipt.
☐ If concealed damage is discovered, stop unpacking
the shipment. Do not remove damaged material
from the receiving location. Take photos of the
damage, if possible. The owner must provide
reasonable evidence that the damage did not occur
after delivery.
☐ Notify the carrier’s terminal of the damage
immediately, by phone and by mail. Request an
immediate, joint inspection of the damage with the
carrier and the consignee.
☐ Notify the Trane sales representative and arrange
for repair. Do not repair the unit, however, until
damage is inspected by the transportation
representative.
Loose Parts Inventory
Check all items against the shipping list. Display,
display arm and mounting, water vessel drain plugs,
isolation pads, and other optional components are
shipped loose in the parts box. Electrical diagrams and
service literature are located inside the Adaptive
Frequency™ Drive (AFD) panel.
Storage
NNoottee:: If the chiller is stored outdoors for any amount of
time, ddoo NNOOTT rreemmoovvee AANNYY sshhiippppiinngg
ccoovveerriinnggss.. PPrrootteecctt tthhee cchhiilllleerr ffrroomm tthhee
eelleemmeennttss aanndd pprrootteecctt aaggaaiinnsstt ffrreeeezziinngg,,
especially if any shipping materials have been
removed.
If the chiller is to be stored more than one month prior
to installation, observe the following precautions:
• Do NOT store the chiller in areas in which the
temperature exceeds 122°F (50.0°C) or the
refrigerant will relieve.
• Do NOT remove the protective coverings from the
electrical panel.
• Store the chiller in a dry, secure area.
• Upon receipt and every three months thereafter,
attach a gauge and manually check the pressure in
the refrigerant circuit. Call a qualified service
organization and the appropriate Trane sales office
if:
– for R-134a, if the refrigerant pressure is below
71 psig at 70°F (489.5 kPaG at 21.1°C) or 46 psig
at 50°F (317.2 kPaG at 10.0°C).
– for R-513A, if the refrigerant pressure is below
77 psig (530.9 kPaG at 21.1°C) at 70°F or 50 psig
at 50°F (344.7 kPaG at 10.0°C).
NNoottee:: Pressure will be approximately 5 psig (34.5
kPaG) if shipped with the optional nitrogen
charge
Installation Requirements and
Contractor Responsibilities
A list of the contractor responsibilities typically
associated with the unit installation process is provided
in the following table.
WWAARRNNIINNGG
CCoommbbuussttiibbllee MMaatteerriiaall!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn
ddeeaatthh oorr sseerriioouuss iinnjjuurryy oorr eeqquuiippmmeenntt ddaammaaggee..
SShhrriinnkk--wwrraapp iiss aa ccoommbbuussttiibbllee mmaatteerriiaall.. AAvvooiidd ooppeenn
ffllaammeess aanndd hhoott ssppaarrkkss..