Viewing and Changing System Status Information
22 BMTW-SVU02C-EN
Making a Manual Request
If your request to override the present value or lighting value cannot be
completed, an override control list displays as shown in Figure 18. This
list shows the control requests in the priority that they will be processed.
The lowest priority number is 16 and the highest is 1. The default for the
BCU operator display is 12. Your priority level depends on the level set by
the Trane programmer or installer.
Figure 18: Override Control List
Press OK to add your request to the priority list. The operator display
returns you to the Manual Control screen, where the override control
status changes to Manual Request (see Figure 19).
Figure 19: Override Control Status—Manual Request
Indicates the requested override
will be made when it becomes
the highest priority level in the
list
Shows the
value that the
property is
currently being
controlled to