The unit is operating in Ventilation Only Mode - not
attempting to Economize and the Commanded Damper
Position is greater than the Current Damper Feedback
Position + 10% for 5 continuous minutes, Outdoor Air
Damper Not Modulating diagnostic is generated.
EExxcceessssiivvee OOuuttddoooorr AAiirr
The unit is operating in Ventilation Only Mode - not
attempting to Economize and the Commanded Damper
Position is less than the Current Damper Feedback
Position - 10% for 5 continuous minutes. Excessive
Outdoor Air diagnostic is generated.
To change the Economizer Control Function to dry
bulb, go to the Configuration Menu on the Human
Interface Module and set Comparative Enthalpy to "Not
Installed".This allows the user to select dry bulb under
the Economizer Control Function which is a Submenu
of the Setup Menu. For additional instructions please
see the Programming and Troubleshooting Guide.