Figure 21. Ductwork conversion
See Detail A
Detail A
Vertical Support
Align Gasket
To Base Rail
Surface
Gasket
1/4ā Thick x 1ā Wide
Gasket to Butt Up to
Vertical Support Surface
Typical Both Sides
Vertical Support/Base Rail Bottom
Gasket Application Details
Base Rail
Unit Rigging and Placement
WWAARRNNIINNGG
HHeeaavvyy OObbjjeecctt!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn
uunniitt ddrrooppppiinngg wwhhiicchh ccoouulldd rreessuulltt iinn ddeeaatthh oorr
sseerriioouuss iinnjjuurryy,, aanndd eeqquuiippmmeenntt oorr pprrooppeerrttyy--oonnllyy
ddaammaaggee..
EEnnssuurree tthhaatt aallll tthhee lliiffttiinngg eeqquuiippmmeenntt uusseedd iiss
pprrooppeerrllyy rraatteedd ffoorr tthhee wweeiigghhtt ooff tthhee uunniitt bbeeiinngg
lliifftteedd.. EEaacchh ooff tthhee ccaabblleess ((cchhaaiinnss oorr sslliinnggss)),, hhooookkss,,
aanndd sshhaacckklleess uusseedd ttoo lliifftt tthhee uunniitt mmuusstt bbee ccaappaabbllee
ooff ssuuppppoorrttiinngg tthhee eennttiirree wweeiigghhtt ooff tthhee uunniitt.. LLiiffttiinngg
ccaabblleess ((cchhaaiinnss oorr sslliinnggss)) mmaayy nnoott bbee ooff tthhee ssaammee
lleennggtthh.. AAddjjuusstt aass nneecceessssaarryy ffoorr eevveenn uunniitt lliifftt..
1. To configure the unit Center-of-Gravity, utilize
TOPSS or contact the local Trane sales office.
2. Attach adequate strength lifting slings to all lifting
lugs. The figures beginning with Figure 23, p. 48
show the minimum distance between the lifting
hook and the top of the unit and illustrate the
installation of spreader bars to protect the unit and
to facilitate a uniform lift. lists typical approximate
minimal unit operating weights. To determine
additional component weight, see .
3. Test lift the unit to ensure it is properly rigged and
balanced, make any necessary rigging adjustments.
4. Lift the unit and position it over the curb and
pedestal. These units have a continuous base rail
around the air handler section which matches the
curb.
IImmppoorrttaanntt:: For replacements, remove old gasket
from the roof curb and place new
gasket material on curb. See ā,ā to
determine gasket material length using
roof curb dimensions.
5. Align the base rail of the unit air handler section
with the curb rail while lowering the unit onto the
curb. Make sure that the gasket on the curb is not
damaged while positioning the unit. (The pedestal
simply supports the unit condenser section)
A cross section of the juncture between the unit and
the roof curb is shown below.
Figure 22. Curb cross section
Gasket
Base Pan
Lifting
Lug
14 1/16
1 13/16
2
1/2
2āx4ā