26
RT-SVX24Q-EN
Seal air gaps around wiring and refrigerant tubing
through bulkhead.
Side panels and top cover assembled between high
and low side.
Verify line dampening weights are installed on each
discharge line.
Unit Rigging and Placement (Three-piece
unit) (in addition to two-piece unit
rigging and placement)
Rail guide attached to evaporator section base rails.
Evaporator section rigged and set onto roof curb,
aligned with supply end.
Removed and discarded shipping protection panels
and top blockoffs from evaporator section.
Removed side panels and roof cap from evaporator
section.
Applied gasket and butyl tape as indicated in the
IOM.
Removed and discarded shipping protection panels
and top block off from outside air section.
Rigged and set outside air section onto roof curb to
within 2" of evaporator section.
Using 0.75" x 24" threaded rod pull and secure
evaporator section and outside air section together.
Using .375" bolts, nuts and washers pull and secure
the roof rails together.
Installed roof splice plate.
Added bullwrap to electrical wiring between
evaporator and outside air section.
Connected power and control wiring between
evaporator and outside air section.
Gasket applied and side panels installed on unit
split.
Butyl tape applied on top of unit split along roof
seam and roof cap installed.
Field Installed Control Wiring—Complete the field
wiring connections for constant volume or variable
air volume controls as applicable. Refer to “Field
Installed Control Wiring” for guidelines.
Main Electrical Power Requirements
Verify that the power supply to the unit complies
with the unit nameplate specification. Refer to Main
Unit Power Wiring in the Installation chapter.
Properly ground the unit.
Inspect all control panel components and tighten
any loose connections.
Connect properly sized and protected power supply
wiring to a field supplied/installed disconnect and
the unit (copper wiring only to the unit).
Verify that phasing to the unit is correct (ABC).
Turn the 1S2 toggle switch off to prevent accidental
unit operation.
Turn on power to the unit.
Press the STOP button on the Human Interface
(1U2).
Verify that all compressor crankcase heaters are
energized for at least 8 hours prior to unit start-up.
IImmppoorrttaanntt:: Note: All field-installed wiring must comply
with NEC and applicable local codes.
Electric Heat Units
Inspect the heater junction box and control panel;
tighten any loose connections.
Check electric heat circuits for continuity.
Two and Three piece units only) Route power
wiring to high side junction box.
Gas Heat Units
Gas supply line properly sized and connected to the
unit gas train.
All gas piping joints properly sealed.
Drip leg installed in the gas piping near the unit.
Gas piping leak checked with a soap solution. If
piping connections to the unit are complete, do not
pressurize piping in excess of 0.50 psig or 14" W.C.
to prevent component failure.
Main supply gas pressure between 7" and 14" W.C.
Flue Tubes clear of any obstructions.
Factory-supplied flue assembly installed on the
unit.
Connect the 3/4" CPVC furnace drain stub-out to a
proper condensate drain.
Install field provided heat tape to furnace drain line.
Hot Water Heat
Route properly sized water piping through the base
of the unit into the heating section.
Install the factory-supplied, 3-way modulating
valve.
Complete the valve actuator wiring.
Steam Heat
Route properly sized steam piping through the base
of the unit into the heating section.
Install the factory-supplied, 2-way modulating
valve.
Complete the valve actuator wiring.
Install 1/2", 15-degree swing check vacuum breaker
(s) at the top of each coil section. Vent breaker(s) to
PPrree--IInnssttaallllaattiioonn

Table of Contents

Related product manuals