the atmosphere or merge with return main at
discharge side of steam trap.
Position the steam trap discharge at least 12" below
the outlet connection on the coil.
Use float and thermostatic traps in the system, as
required by the application.
O/A Pressure Sensor and Tubing
Installation (All VAV units and CV units
with return fan or StatiTrac)
O/A pressure sensor mounted to the roof bracket.
Factory supplied pneumatic tubing installed
between the O/A pressure sensor and the connector
on the vertical support.
(Units with StatiTrac) Field supplied pneumatic
tubing connected to the proper fitting on the space
pressure transducer located in the filter section, and
the other end routed to a suitable sensing location
within the controlled space.
Evaporative Condenser
Remove fan bracket.
Hookup inlet and drain piping.
Install heat tape if needed.
Setup drain hold or drain on power loss.
Setup Mechanical Float.
Setup drain time.
Setup water quality management (3rd party
system).
Options setup.
Calibrate Conductivity Controller.
Setup blowdown setpoints on the conductivity
sensor.
Energy Recovery Wheel
Verify that the wheel turns freely though a full
rotation.
Confirm that all wheel segments are fully engaged
in the wheel frame and that the segment retainers
are completely fastened.
Confirm the seal adjustment and proper belt
tracking on the wheel rim.
PPrree--IInnssttaallllaattiioonn