Installation
60 RT-SVX36K-EN
Table 23. Electrical service sizing data — motors — 20-130 tons
Nominal
Tons
Nominal Voltage
200
FLA
230
FLA
460
FLA
575
FLA
Air-Cooled Condenser Fan Motor
20 8.2 8.2 3.6 2.8
25 12.3 12.3 5.4 4.2
30 12.3 12.3 5.4 4.2
40 16.4 16.4 7.2 5.6
50, 55 24.6 24.6 10.8 8.4
60 24.6 24.6 10.8 8.4
70 24.6 24.6 10.8 8.4
75 24.6 24.6 10.8 8.4
90 N/A N/A 14.4 11.2
105 N/A N/A 18.0 14.0
115 N/A N/A 18.0 14.0
130 N/A N/A 21.6 16.8
Motor Horsepower Supply
(a)
/Exhaust/Return Fan Motor
(b)
(4 pole)
3 11.0 8.6 4.3 3.8
5 15.3 13.2 6.6 5.4
7.5 22.2 18.8 9.4 7.8
10 29.5 25.2 12.6 10.1
15 40.7 35.4 17.7 15.1
20 56.1 49.4 24.7 19.6
25 70.5 62.0 31.0 24.5
30 85.5 73.2 36.6 29.2
40
(c)
N/A N/A 49.0 39.0
50
(c)
N/A N/A 60.5 48.0
Motor Horsepower Supply Fan Motor (6 pole)(a)
(d)
3 10.1 8.8 4.4 3.7
5 17.0 14.8 7.4 5.8
7.5 25.0 22.0 11.0 8.6
10 32.0 28.6 14.3 11.5
15 46.0 41.0 20.5 16.0
20 63.0 54.0 27.0 NA
(a)FLA is for individual motors by HP, not total unit supply fan HP.
(b)Return fan motors are available in 3-20 Hp
(c) 40 & 50 Hp motor available as standard in 460 & 575 volt only.
(d)DDP fans selected under 1,700 RPM will have 6-pole motors