11 6 RT-SVD03G-EN
ReliaTel Control Temporary Operation 3-25 tons
Temporary comfort can be provided without a Zone Sensor Module or thermostat in place by using
the Outdoor Air Sensor or a spare Supply Air / Return Air Sensor. How to do it: remove the sensor
from the unit, add enough thermostat wire to it so that it can be placed in the return air stream, then
connect the sensor to J6-1 & J6-2.
After the permanent Zone Sensor or thermostat is in place, the sensor must be removed from J6-
1 & J6-2.
If the RTRM does not have a space temperature input (J6-1, J6-2), or have a conventional
thermostat input (G, Y, W), the unit will not run (except in the test mode).
Temporary Sensor (thermistor) attached to J6-1 and J6-2 only:
Continuous fan
Auto changeover
74°F cooling, 71°F heating
Note: 27½-50 ton units - the outdoor air sensor should not be used for this purpose.
Figure 68. ReliaTel Refrigeration Module
ReliaTel Refrigeration Module
place sensor in return
air stream
connect sensor to
terminals 1&2