98 RT-SVD03G-EN
ReliaTel Economizer Actuator Layout
Remove the screw in the center of the actuator module. Remove the actuator module (this will not
be used). Then, remove the wiring from the module.
Terminals that are exposed by removal of the actuator module are ¼" spades labeled 24 VAC, TR
& TR1 and 2-10 VDC IN (+/-)
Apply 24 VAC to TR and TR1 and 2-10 VDC signal to (+/-) on 2-10 VDC IN.
DO NOT USE the lower terminals labeled 2-10 VDC OUT.
Figure 59. ReliaTel Economizer Terminals