Trane ReliaTel - Modulating Dehumidification with Hot Gas Reheat (27.5-50 Tons); Controls Overview

Trane ReliaTel
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
128 RT-SVD03G-EN
Modulating Dehumidification with Hot Gas Reheat
(27.5-50 Tons)
Controls Overview
Reheat LPC (RTDM input)
Manual lockout after four trips.
Additional 60# low pressure cutout ignored for the first 10 minutes of compressor run time
in reheat mode.
Will also be active during service test.
Two Modulating valves are controlled by the leaving unit temperature sensor
Cooling mode: Cooling valve 100% open, Reheat valve 0% open.
Reheat mode: Cooling and Reheat valves open/close inverse of each other. Reheat valve
allowed to operate from 15 to 85% open.
Reheat pump out solenoid
Energized when in cooling mode. It is inactive in all other modes.
A three minutes purge cycle will take place after one continuous hour (hard coded) of
operation in reheat or cooling mode.
Entering Evaporator Temperature (overrides Frostat during reheat)
During reheat operation if the temp is below 35º F for 10 minutes the control will shed
compressors (or circuits).
The unit will not be allowed to stage up until leaving reheat.
If the temp is below 35º F for 10 more continuous minutes all compressors will stage off and
the ID fan will continue to run.
Once reaching 45º F the compressor (circuit) will be re-enabled.
The condenser fans will be staged differently in reheat mode than cooling mode.
Single circuit units (3 total condenser fans): A maximum of 2 outdoor fans above 85º F and
a maximum of 1 outdoor fan below 80º F.
Dual circuit units (4 total condenser fans): A maximum of 4 outdoor fans above 85º F and
a maximum of 2 outdoor fans below 80º F.
Service mode operation
Reheat step will follow the last cooling step in service test mode.
All compressors energized.
Reheat / Cooling Modulating valve positions are 50%.
Pump out solenoid de-energized.
60 minute service test interval timer will be in control.