Modulating Dehumidification with Hot Gas Reheat (27.5-50 Tons)
RTRM handles the main dehumidification logic.
RTOM contains the humidity and supply air set point.
RTDM (New module) handles the reheat/cooling valve and pump out relay control.
Customer adjustable set points
Supply air reheat set point located on RTOM (65-80ºF default 70ºF)
Dehumidification (humidity) set point located on RTOM (40-65% default 50%)
VAV Dehumidification Override Zone Cooling and Heating Set points (75ºF Cooling, 68ºF
Heating). A customer can adjust them if a CV Remote Zone sensor is connected to the RTRM
or by using resistors.
Figure 72. Voyager Commercial Modulating Hot Gas Reheat