148 RT-SVD03G-EN
Voyager Commercial 27½ to 50 Tons CV and VAV
Configuration Input
Note: The unit is hard wired with specific inputs as indicated below. These inputs cause the unit
to respond with the appropriate outputs. Configuration inputs are only recognized at unit
power-up.
Where “GND” is indicated below, the input is connected to chassis ground. Where “JUMPER” is
indicated below, both connection points are shown.
Unit Type
RTOM
J3-5
RTRM
J1-3,J1-5
V3 GND
V2, Precedent Open
Non Heat Pump Jumper
Cond Fan Cycling RTOM J3-4
27.5-30 Ton GND
35 Ton Open
40 Ton GND
50 Ton Open
SA Tempering
(CV Units Only)
RTOM
J3-1,J3-2
Enabled Open
Disabled Jumper
Electric Heat RTRM J2-1,J2-2
Heat Open
No Heat Jumper
3 Compressor RTRM J3-7
27.5-35 Ton Open
40-50 Ton GND
Lead/Lag RTRM J3-8
Disabled GND
Enabled Open
Modulating Gas RTOM J3-3
No Modulating Gas Open
Modulating Gas Ground
High Heat (2 Heat
Exchangers) IGN #2 J1-5
High Heat Ground