ReliaTel LED Functions
ReliaTel Dehumidification Module (RTDM)
Green system LED
NA - No Onboard LED
Economizer Actuator Module (ECA)
Green system LED
On: OK to economize
Slow flash: Not OK to economize
Fast flash: Not communicating with RTRM
OFF: No power or system failure
1/2 second on, 2 seconds off: no communication
Error codes — 1/2 second on, 1/4 second off
1 flash – Actuator fault
2 flash – CO2 sensor
3 flash – RA humidity sensor
4 flash – RA temp sensor
6 flash – OA humidity sensor
7 flash – No Communication with RTRM or OAT sensor has failed.
8 flash – MA temp sensor
9-11 flash – Internal fault
Ignition Control (IGN)
Note: See ignition control section for specific flash code schedule.
Green
On: Normal no call for heat
Slow flash: Active call for heat
Fast flash: Not communicating with RTRM
Error codes
2 flash – system lockout – failure to sense flame
3 flash – pressure switch failure to close when CBM stops or open when CBM starts (not
applicable to 12½ to 50 tons)
4 flash – TCO circuit open
5 flash – Flame being sensed yet gas valve not energized
6 flash - Flame Rollout (FR) circuit open (Not applicable to 12½ to 50 tons)