124 RT-SVD03G-EN
ReliaTel Ventilation Override
Three Ventilation modes are available with ReliaTel through use of an Options Module (RTOM) and
economizer (ECA) with Power Exhaust. Following is a list of each mode and what happens during
each.
Connections to the unit to accomplish Ventilation Modes are shown below. All three inputs are
shown for illustration; only one is typically used.
Note: Although not associated with ventilation override, humidistat connections for
dehumidification are also provided on this terminal block.
Emergency shutdown from the LTBI 5&6 will override any ventilation override mode.
Ventilation override inputs override smoke detector inputs through the RTOM. (3-25 tons only).
Table 44.
Supply Fan forced:
IGV/
VFD*
Compressors
may run?
OK to heat
(gas/elect.)?
Economizer
position?
Power
Exhaust?
Exhaust
Damper
1.
VHR
Relay*
Pressurization ON 100% No No 100% Off 0% ON
Purge ON 100% No No 100% On 100% ON
Exhaust OFF 100% No No 0% On 100% ON
*Voyager 27.5 - 50 tons VAV
1. Exhaust Damper is controlled on units with Power Exhaust w/ Statitrac.