154 RT-SVD03G-EN
Voyager Commercial 27½ to 50 Tons CV and VAV
For remote setpoint cut this jumper:
Supply Air Pressure Setpoint R64
Supply Air Cooling Setpoint R69
Supply Air Heating Setpoint R75
Supply Air Reset Amount R68
Supply Air Pressure Deadband R67
Morning Warm-up Setpoint R63
Supply Air Reset Setpoint R66
Note: Remote SA Cooling Setpoint can be installed on RTAM J7-2, 3 (as shown) or on RTRM J6-
2, 3. If the SA Cooling Setpoint is installed on RTRM J6-2, 3 or a BAYSENS021* is being used;
see VAV Supply Air Cooling remote setpoint - BAYSENS021*.
Morning Warm-up:
Is allowed even if DWU is disabled.
Enabled by transition from unocc to occup (power reset, emergency reset will not do it)
Unoccupied Heating:
Is allowed even if DWU is disabled
Supply Air Heating
40-150 deg F +/- 2 deg F
5 Minute Changeover Heat/Cool Input
Changeover input required
Figure 86. RTAM module
Static
pressure
setpoint
Static
pressure
deadband
For remote deadband cut
this jumper
Reset
setpoint
Supply Air Heating
Setpoint
R66
Reset
amount
Supply air
cooling
setpoint
Morning
warmup
setpoint
R63
R68
R69
R67R64
1 2 3 4 5 6 7 8 9 10 11 12
Remote setpoint
terminal strip
12345
SW1
Supply Air (Static) Pressure S.P.
DIP switch
1
IGU Config
Reset Select
DWU Enable
VAV w/o IGV
IGV - OFF OFF
VFD - ON OFF
12
No Reset OFF OFF
Return Air OFF ON
Zone Temp ON OFF
Outdoor Air ON ON
34
5
DWU Disable OFF
DWU Enable ON
ON
Supply Air Cooling Setpoint
Supply Air Reset Amount
Supply Air (Static) Pressure Deadband
Morning Warmup Setpoint
Supply Air Reset Setpoint
OFF ON
ON ON
23
45
SW1
R 75
13 14
Supply Air Heating Setpoint
J5
1
2
LTB-S
Changeover input (VAV only)