RT-SVD03G-EN 163
Software Change History
ECA
V1.05 4/12/01 X13650878020 -Initial production release - W7399A, W7340A.
V2.05 7/15/02 X13650878020 -Fixed 60 seconds communication loss.
V2.07 10/21/03 X13650878060
-Changed to Masked chip.
-Fixed comparative enthalpy.
V2.08 8/25/04 X13650878080 -Went back to OTP chip to resolve Masked chip problems.
V1.0 4/1/05 X13651082010 -Upgraded ECA actuator and module W7399B, W7340B
V1.0 4/1/05 X13651082020 -First production ECA manual with ALL sensor inputs.
V1.0 4/1/05 X13651081010 -First production release of ECA module with dry bulb only input.
RTEM
V1.1 03/2010 X13651513-01
-Initial Release full configuration logic module.
-DCV updated to meet ASHRAE 62.1 2007.
-DCV Mode Configuration input added.
-Changed that a minimum position provided from BAS would have priority over all
local damper position requests, including DCV.
V1.1 03/2010 X13651514-01 -Initial Release dry bulb only module.
RTDM
V1.2 03/2010 X13651466-02
-Initial Release
-V3 Modulating Dehumidification Support
RTAM
V2.0 01/2004 X13650871-01 -Initial release to support VAV for V3.
V2.2 08/2004 X13650871-01 -Enhancements to IGV/VFD control.
V3.0 12/2007 X13650871-02 -Added Supply Air Heating Setpoint to be used with Modulating Gas Heat units.
V3.1 09/2010 X13650871-02
-Fixed SA Pressure input conversion logic so that when systems start the VAV Box
fans the negative pressure does not cause the SA Pressure reading to go invalid and
cause a temporary SA Pressure Failure until the ID Fan starts.
TCI
V1.3 4/16/01 X13650869010 -First production release.
V1.23 12/31/01 X13650869010 -Fix a variety of false diagnostics.
V1.24 1/25/01 X13650869010
-Revised to allow true discharge air sensor to be reported through RTOM if unit
doesn’t have economizer option.
V3.1 3/10/04 X13650869030
-Add status LED support and VAV enhancements.
-Added code to fix VAV lockup.
LCI-SCC
V1.02 4/16/01 X13650870010 -First production release.
V2.06 10/01/03 X13650870020 -Fixed to allow stand-alone operation without communication link.
LCI-DAC
V1.0 4/01/04 X1365106601 -LCI for VAV Voyager 3
LCI-SSC
2.06 3/10/04 X13650870-02
Feature Enhancement:
-Add support for nviSpaceRH - Communicated SpaceRH
-Add support for nviOutdoor Temp - Communicated Outdoor Air Temperature
-Add support for nviOutdoorRH - Communicated Outdoor RH
-Add support for nviTraneVar1401 - Communicated Service Test
-Add support for nviBldgStatPress - Not Supported in RTRM
-Add support for nvoMixedAirTemp - Reports Mixed Air temperature
-Add support for nvoBldgStatPress - Not Supported in RTRM
-Add support for nciSpaceRHSetpt - Communicated Space RH Set Point
-Add support for nciExhaustConfig - Communicated Exhaust Fan Start Position
-Add support for nciBldgStaticSP - Not Supported in RTRM
Bug Fix:
-Fixed bug to allow communicated Emergency Heat Mode
2.07 11/1/04 X13650870-02
Bug Fix:
-Fix Active Set point to report the cooling set point during dehumidification mode
instead of 32
2.08 1/15/07 X13650870-02
Bug Fix:
-Fix the ApplicMode to change if the unit is in dehumidification when using a BAS in
optimal start & nite purge