EasyManua.ls Logo

Trane ReliaTel - Page 40

Trane ReliaTel
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
40 RT-SVD03G-EN
ReliaTel Option Module (RTOM)
Table 8. RTOM Supply Air Reheat Setpoint
Voltage (Vdc) Setpoint (ºF) Voltage (Vdc) Setpoint (ºF)
0.002 65 1.683 73
0.169 65.5 1.766 73.5
0.317 66 1.822 74
0.395 66.5 1.887 74.5
0.552 67 1.940 75
0.672 67.5 1.998 75.5
0.785 68 2.064 76
0.915 68.5 2.118 76.5
1.028 69 2.175 77
1.114 69.5 2.196 77.5
1.206 70 2.234 78
1.275 70.5 2.275 78.5
1.365 71 2.318 79
1.445 71.5 2.368 79.5
1.525 72 2.415 80
1.610 72.5
Table 9. RTOM Dehumidification Setpoint
Voltage (Vdc) Setpoint (%) Voltage (Vdc) Setpoint (%)
0.002 40 1.745 53
0.238 41 1.824 54
0.445 42 1.853 55
0.539 43 1.929 56
0.677 44 1.978 57
0.811 45 2.07 58
0.984 46 2.136 59
1.117 47 2.184 60
1.245 48 2.259 61
1.349 49 2.268 62
1.428 50 2.324 63
1.552 51 2.397 64
1.625 52 2.448 65