Thermostats and Sensors
BAYSENS106*/ASYSTAT106*
Accessory Heat / Cool Zone Sensor Module (ZSM) single set point, manual changeover. Four
conductors required.
BAYSENS107A/ASYSTAT107A
Accessory Heat Pump Zone Sensor Module (ZSM) single set point, manual changeover. Six
conductors required.
Figure 37. BAYSENS106A/ASYSTAT106A
Figure 38. BAYSENS107A/ASYSTAT107A
2
4
Calibration
Pot 1 (see )Note 1
Note 1:
Pot 1 is
factory
calibrated.
Field
adjustment
voids
warranty.
3
R6, 8.45 k
R1, 4.87 k
R2, 2.32 k
R3, 19.6 k
Heat
Off
Cool
RT1 thermistor,
10 k at 25°C
1
R11, zero
Signal common
Cool setpoint (CSP)
Mode
(Sys/Fan switch)
Zone
temperature
TB1
Auto
On
Temperature
setpoint
Pot 5,
1 k
System
SW1
Fan
SW2
Part Number – SEN01515
RT1 thermistor,
10 k at 25°C
Temperature
setpoint
Pot 5,
1 k
1
2
4
Calibration
Pot 1 (see )Note 1
Note 1:
Pot 1 is
factory
calibrated.
Field
adjustment
voids
warranty.
3
R6, 8.45 k
Auto
On
R1, 4.87 k
R2, 2.32 k
R3, 19.6 k
Heat
Off
Cool
Fan
SW2
R4, 34.8 k
EM Heat
CR3
Green
6
7
LED Heat
LED Common
TB2
R9, zero
Signal common
Cool setpoint (CSP)
Zone
temperature
TB1
Mode
(Sys/Fan switch)
System
SW1
Part Number – SEN01528