19
Symbio™ 700 Unit LED Functions
LED 1 – P7-1 (Black) SOLID ON=When output is on, OFF=When output is off
LED 2 – P7-3 (Black) SOLID ON=When output is on, OFF=When output is off
LED 3 – Bluetooth
OFF = Bluetooth radio is not available
ON = Active Bluetooth connection in process
BLINKING = Controller is waiting for a Bluetooth connection
LED 4 – P7-5 (Black) SOLID ON=When output is on, OFF=When output is off
LED 5 – P8-5 (Red) SOLID ON=When output is on, OFF=When output is off
LED 6 – P8-6 (Red) SOLID ON=When output is on, OFF=When output is off
LED 7 – Ethernet
SOLID ON = When link is connected
OFF = When link is disconnected
LED 8 – Ethernet BLINKING = Activity on link, OFF = No activity on link
LED 9 – System
SOLID GREEN = All objects in a normal state
OFF = Controller not powered or is in an alarm condition
LED 10 – Alarm Status
BLINKING RED = At least one object is in a not normal state
OFF = Controller not powered or is in a normal state
(VFD) TX BLINKING GREEN = when Modbus data is sent
(VFD) RX BLINKING YELLOW = when Modbus data is received
LED 13 – IMC (Options board) IMC Link TX BLINKING GREEN = when IMC data is sent
LED 14 – IMC (Options Board) IMC Link RX BLINKING YELLOW = when IMC data is received
LED 15 – P9-5 (White) SOLID ON=When output is on, OFF=When output is off
LED 16 – P9-6 (White) SOLID ON=When output is on, OFF=When output is off
LED 17 – P10-5 (Blue) SOLID ON=When output is on, OFF=When output is off
LED 18 – P10-6 (Blue) SOLID ON=When output is on, OFF=When output is off
LED 19 – P11-1 (White) SOLID ON=When output is on, OFF=When output is off
LED 20 – P11-3 (White) SOLID ON=When output is on, OFF=When output is off
LED 21 – P5-2 SOLID ON=When output is on, OFF=When output is off
LED 22 – P5-4 SOLID ON=When output is on, OFF=When output is off
LED 23 – BACnet MS/TP Link RX BLINKING YELLOW = when BACnet data is received