Supply Fan Minimum Speed Setpoint
Range: 0-100%
Operation:
0-100% over minimum to effective maximum VFD configured fan speed
Example: VFD Min = 30Hz, Effective VFD Max = 60Hz
Supply Fan Minimum Speed Setpoint @ 50% yields 45Hz VFD output.
Minimum and Maximum Speed Setpoints interact to ensure that the minimum defined fan speed at a
given equipment operating condition is maintained.
Supply Fan Percentages
Multi-speed minimum supply fan speeds
Variable speed minimum supply fan speeds