5-56 Term. 33 High Frequency
Range: Function:
100 Hz* [0 - 110000 Hz] Enter the high frequency corresponding to the high motor shaft speed
(i.e., high reference value) in par.5-58
Term. 33 High Ref./Feedb. Value.
5-57 Term. 33 Low Ref./Feedb. Value
Range: Function:
0.000 N/
A*
[-999999.999 - 999999.999
N/A]
Enter the low reference value [RPM] for the motor shaft speed. This is
also the low feedback value, see also par.5-52
Term. 29 Low Ref./Feedb.
Value.
5-58 Term. 33 High Ref./Feedb. Value
Range: Function:
100.000
N/A*
[-999999.999 - 999999.999
N/A]
Enter the high reference value [RPM] for the motor shaft speed. See also
par.5-53
Term. 29 High Ref./Feedb. Value.
5-59 Pulse Filter Time Constant #33
Range: Function:
100 ms* [1 - 1000 ms] Enter the pulse filter time constant. The low-pass filter reduces the in-
fluence on, and dampens oscillations in, the feedback signal from the
control.
This is an advantage, if, for example, there is a great amount of noise in
the system. This parameter cannot be adjusted while the motor is run-
ning.
5-6* Pulse Outputs
Parameters for configuring the scaling and output functions of pulse outputs. The pulse outputs are designated
for terminals 27 or 29. Select terminal 27 output in par.5-01
Terminal 27 Mode and terminal 29 output in par.
5-02
Terminal 29 Mode.
Options for readout output variables:
Parameter Description
TR200 Programming Guide 4-79