Parameters for configuring the option control word profile.
8-10 Control Profile
Option: Function:
Select the interpretation of the control and status words corresponding
to the installed serial communication bus. Only the selections valid for
the serial communication bus installed in slot A will be visible in the
keypad display.
[0] * FC profile
[1] PROFIdrive profile
[5] ODVA
[7] CANopen DSP 402
8-13 Configurable Status Word STW
Option: Function:
This parameter enables configuration of bits 12 – 15 in the status word.
[0] No function
[1] * Profile Default Function corresponds to the profile default selected in par.8-10
Control
Profile.
[2] Alarm 68 Only Only set in the event of Alarm 68.
[3] Trip excl Alarm 68 Set in the event of a trip, except if the trip is executed by Alarm 68.
[16] T37 DI status The bit indicates the status of terminal 37.
“0” indicates T37 is low (safe stop)
“1” indicates T37 is high (normal)
8-3* Adjustable Frequency Drive Port Settings
Parameters for configuring the Adjustable Frequency Drive Port.
8-30 Protocol
Option: Function:
Protocol selection for the integrated FC (standard) Port (RS485) on the
control card.
Parameter group 8-7* is only visible when Adjustable Frequency Drive
Option [9] is chosen.
[0] * FC
Communication according to the FC protocol as described in the TR200
Design Guide, RS 485 Installation and Set-up
.
[1] FC MC
Same as
FC
[0] but to be used when downloading SW to the adjustable
frequency drive or uploading dll file (covering information regarding pa-
rameters available in the adjustable frequency drive and their inter-
dependencies) to Trane Drive Utility, TDU.
[2] Modbus RTU Communication according to the Modbus RTU protocol as described in
the TR200
Design Guide, RS 485 Installation and Set-up
.
[3] Metasys N2 Communication protocol. The N2 software protocol is designed to be
general in nature in order to accommodate the unique properties each
TR200 Programming Guide 4-95