device may have. Please see separate manual
TR200 MetasysMG.
12.NX.YY
.
[4] FLN
[9] FC Option To be used when a gateway is connected to the integrated RS 485 port,
e.g., the BACnet gateway.
The following changes will take place:
-The address for the adjustable frequency drive port will be set to 1 and
par.8-31
Address, is now used to set the address for the gateway on the
network, e.g., BACnet.
-Baud rate for the Drive port will be set to a fixed value (115,200 Baud)
and par.8-32
Baud Rate is now used to set the baud rate for the network
port (e.g., BACnet) on the gateway.
[20] LEN
NOTE: Further details can be found in the Metasys manual.
8-31 Address
Range: Function:
Applica-
tion de-
pend-
ent*
[Application dependant]
8-33 Parity / Stop Bits
Option: Function:
Parity and Stop Bits for the protocol par.8-30
Protocol using the Adjust-
able Frequency Drive Port. For some of the protocols, not all options will
be visible. Default depends on the protocol selected.
[0] * Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Range: Function:
Applica-
tion de-
pend-
ent*
[Application dependant]
8-36 Maximum Response Delay
Range: Function:
Applica-
tion de-
pend-
ent*
[Application dependant]
4-96 TR200 Programming Guide