[1] Continuously Choose whether the device should send the "I-Am" service message only
at power-up or continuously with an interval of approx. 1 min.
NOTE: This parameter is active only when par.8-30
Protocol is set to [9]
Option
.
8-75 Initialization Password
Range: Function:
Applica-
tion de-
pend-
ent*
[0 - 0 N/A] Enter the password needed for execution of Drive Re-initialization from
BACnet.
NOTE: This parameter is active only when par.8-30
Protocol is set to [9]
Drive Option
.
8-8* Adjustable Frequency Drive Port Diagnostics
These parameters are used for monitoring the bus communication via the Adjustable Frequency Drive Port.
8-80 Bus Message Count
Range: Function:
0 N/A* [0 - 0 N/A] This parameter shows the number of valid messages detected on the
bus.
8-81 Bus Error Count
Range: Function:
0 N/A* [0 - 0 N/A] This parameter shows the number of messages with faults (e.g., CRC
fault), detected on the bus.
8-82 Slave Messages Rcvd
Range: Function:
0 N/A* [0 - 0 N/A] This parameter shows the number of valid messages addressed to the
slave, sent by the adjustable frequency drive.
8-83 Slave Error Count
Range: Function:
0 N/A* [0 - 0 N/A] This parameter shows the number of error messages, which could not
be executed by the adjustable frequency drive.
8-84 Slave Messages Sent
Range: Function:
0 N/A* [0 - 0 N/A]
8-85 Slave Timeout Errors
Range: Function:
0 N/A* [0 - 0 N/A]
Parameter Description
4-100 TR200 Programming Guide