Parameters for reading the motor status values.
16-10 Power [kW]
Range: Function:
0.00
kW*
[0.00 - 10000.00 kW] View the motor power in kW. The value shown is calculated on the basis
of the actual motor voltage and motor current. The value is filtered, and
therefore approx. 30 ms may pass from when an input value changes to
when the data readout values change.
16-11 Power [hp]
Range: Function:
0.00 hp* [0.00 - 10000.00 hp] View the motor power in HP. The value shown is calculated on the basis
of the actual motor voltage and motor current. The value is filtered, and
therefore approximately 30 ms may pass from when an input value
changes to when the data readout values change.
16-12 Motor voltage
Range: Function:
0.0 V* [0.0 - 6000.0 V] View the motor voltage, a calculated value used for controlling the mo-
tor.
16-13 Frequency
Range: Function:
0.0 Hz* [0.0 - 6500.0 Hz] View the motor frequency, without resonance dampening.
16-14 Motor Current
Range: Function:
0.00 A* [0.00 - 10000.00 A] View the motor current measured as a mean value, IRMS. The value is
filtered, and thus approximately 30 ms may pass from when an input
value changes to when the data readout values change.
16-15 Frequency [%]
Range: Function:
0.00 %* [-100.00 - 100.00 %]
16-16 Torque [Nm]
Range: Function:
0.0 Nm* [-30000.0 - 30000.0 Nm] View the torque value with sign, applied to the motor shaft. Linearity is
not exact between 110% motor current and torque in relation to the rated
torque. Some motors supply more than 160% torque. Consequently, the
minimum and maximum values will depend on the maximum motor
current, as well as the motor type being used. The value is filtered, and
thus approx. 1.3 seconds may pass from when an input changes value
to when the data readout values change.
16-17 Speed [RPM]
Range: Function:
0 RPM* [-30000 - 30000 RPM] View the current motor RPM.
TR200 Programming Guide 4-141