16-18 Motor Thermal
Range: Function:
0 %* [0 - 100 %] View the calculated thermal load on the motor. The cut-out limit is 100%.
The basis for calculation is the ETR function selected in par.1-90
Motor
Thermal Protection.
16-22 Torque [%]
Range: Function:
0 %* [-200 - 200 %] This is a readout parameter only.
Shows the actual torque yielded in percentage of the rated torque, based
on the setting of the motor size and rated speed in par.1-20
Motor Power
[kW] or par.1-21 Motor Power [HP] and par.1-25 Motor Nominal Speed.
This is the value monitored by the
Broken Belt Function
set in par. 22-6*.
Parameters for reporting the status of the adjustable frequency drive.
16-30 DC Link Voltage
Range: Function:
0 V* [0 - 10000 V] View a measured value. The value is filtered with an 30 ms time constant.
16-32 Brake Energy /s
Range: Function:
0.000
kW*
[0.000 - 10000.000 kW] View the braking energy transmitted to an external brake resistor, stated
as an instantaneous value.
16-33 Brake Energy /2 min
Range: Function:
0.000
kW*
[0.000 - 10000.000 kW] View the braking energy transmitted to an external brake resistor. The
mean power is calculated on an average basis for the most recent 120
seconds.
16-34 Heatsink Temp.
Range: Function:
0 C* [0 - 255 C]
16-35 Inverter Thermal
Range: Function:
0 %* [0 - 100 %] View the percentage load on the inverter.
16-36 Inv. Nom. Current
Range: Function:
Applica-
tion de-
pend-
ent*
[0.01 - 10000.00 A] View the inverter nominal current, which should match the nameplate
data on the connected motor. The data are used for calculation of torque,
motor protection, etc.
4-142 TR200 Programming Guide