16-91 Alarm word 2
Range: Function:
0 N/A* [0 - 4294967295 N/A] View the alarm word 2 sent via the serial communication port in hex
code.
16-92 Warning Word
Range: Function:
0 N/A* [0 - 4294967295 N/A] View the warning word sent via the serial communication port in hex
code.
16-93 Warning word 2
Range: Function:
0 N/A* [0 - 4294967295 N/A] View the warning word 2 sent via the serial communication port in hex
code.
16-94 Ext. Status Word
Range: Function:
0 N/A* [0 - 4294967295 N/A] Returns the extended status word sent via the serial communication port
in hex code.
16-95 Ext. Status Word 2
Range: Function:
0 N/A* [0 - 4294967295 N/A] Returns the extended warning word 2 sent via the serial communication
port in hex code.
16-96 Maintenance Word
Range: Function:
0 N/A* [0 - 4294967295 N/A] Readout of the Preventive Maintenance Word. The bits reflect the status
for the programmed preventive maintenance events in parameter group
23-1*. 13 bits represent combinations of all the possible items:
Bit 0: Motor bearings
Bit 1: Pump bearings
Bit 2: Fan bearings
Bit 3: Valve
Bit 4: Pressure transmitter
Bit 5: Flow transmitter
Bit 6: Temperature transmitter
Bit 7: Pump seals
Bit 8: Fan belt
Bit 9: Filter
Bit 10: Drive cooling fan
Bit 11: Drive system health check
Bit 12: Warranty
Bit 13: Maintenance Text 0