EasyManua.ls Logo

Trane TR200 - Page 187

Trane TR200
297 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Bit 14: Maintenance Text 1
Bit 15: Maintenance Text 2
Bit 16: Maintenance Text 3
Bit 17: Maintenance Text 4
Position 4
Valve Fan bear-
ings
Pump bear-
ings
Motor bear-
ings
Position 3
Pump seals Tempera-
ture trans-
mitter
Flow trans-
mitter
Pressure
transmitter
Position 2
Drive sys-
tem health
check
Drive cool-
ing fan
Filter Fan belt
Position 1
Warranty
0
hex
- - - -
1
hex
- - - +
2
hex
- - + -
3
hex
- - + +
4
hex
- + - -
5
hex
- + - +
6
hex
- + + -
7
hex
- + + +
8
hex
+ - - -
9
hex
+ - - +
A
hex
+ - + -
B
hex
+ - + +
C
hex
+ + - -
D
hex
+ + - +
E
hex
+ + + -
F
hex
+ + + +
Example:
The Preventive Maintenance Word shows 040Ahex.
Position
1 2 3 4
hex value 0 4 0 A
The first digit 0 indicates that no items from the fourth row requires
maintenance
The second digit 4 refers to the third row indicating that the drive cooling
fan requires maintenance
The third digit 0 indicates that no items from the second row requires
maintenance
The fourth digit A refers to the top row indicating that the valve and the
pump bearings require maintenance
Parameter Description
4-150 TR200 Programming Guide

Table of Contents

Other manuals for Trane TR200

Related product manuals