Maintenance item (e.g., “Motor Bearings”)
Maintenance action (e.g., “Replace”)
Maintenance Time Base (e.g., “Running Hours” or a specific date and time)
Maintenance Time Interval or the date and time of next maintenance
NOTE
To disable a preventive maintenance event, the associated par.23-12 Maintenance Time Base must be set to
Disa-
bled
[0].
Preventive Maintenance can be programmed from the keypad, but use of the PC-based Motion Control Tool
Trane Drive Utility is recommended.
The keypad indicates (with a wrench-icon and an “M”) when it is time for a preventive maintenance action, and
can be programmed to be indicated on a digital output in parameter group 5-3*. The Preventive Maintenance
Status may be read in par.16-96
Maintenance Word. A preventive maintenance indication can be reset from a
digital input, the adjustable frequency drive bus or manually from the keypad through par.23-15
Reset Mainte-
nance Word.
A maintenance log with the latest 10 logs can be read from parameter group 18-0* and via the Alarm log button
on the keypad after selecting Maintenance Log.