23-13 Maintenance Time Interval
Range: Function:
1 h* [1 - 2147483647 h] Set the interval associated with the current preventive maintenance
event. This parameter is only used if
Running Hours
[1] or
Operating
Hours
[2] is selected in par.23-12 Maintenance Time Base. The timer is
reset from par.23-15
Reset Maintenance Word.
Example:
A preventive maintenance event is set up for Monday at 8:00. par.
23-12
Maintenance Time Base is
Operating hours
[2] and par.23-13 Main-
tenance Time Interval is 7 x 24 hours=168 hours. The next maintenance
event will be indicated the following Monday at 8:00. If this maintenance
event is not reset until Tuesday at 9:00, the next occurrence will be the
following Tuesday at 9:00.
23-14 Maintenance Date and Time
Range: Function:
Applica-
tion de-
pend-
ent*
[Application dependant]
23-15 Reset Maintenance Word
Option: Function:
Set this parameter to
Do reset
[1] to reset the Maintenance Word in par.
16-96
Maintenance Word and reset the message displayed in the
keypad. This parameter will change back to
Do not reset
[0] when press-
ing OK.
[0] * Do not reset
[1] Do reset
NOTE
When messages are reset - Maintenance Item, Action and Maintenance Date/Time are not cancelled. par.23-12 Main-
tenance Time Base is set to Disabled [0].
23-16 Maintenance Text
Range: Function:
0 N/A* [0 - 0 N/A]
23-5* Energy Log
The adjustable frequency drive is continuously accumulating the consumption of the motor controlled, based
on the actual power yielded by the adjustable frequency drive.
These data can be used for an Energy Log function allowing the user to compare and structure the information
about the energy consumption related to time.
There are basically two functions:
Parameter Description
TR200 Programming Guide 4-199