23-50 Energy Log Resolution
Option: Function:
Select the desired type of period for logging of consumption. Hour of
Day [0] , Day of Week [1] or Day of Month [2]. The counters contain the
logging data from the programmed date/time for start (par.23-51
Period
Start) and the numbers of hours/days as programmed for (par.23-50 En-
ergy Log Resolution).
The logging will start on the date programmed in par.23-51
Period
Start, and continue until one day/week/month has gone. Last 24 Hours
[5], Last 7 Days [6] or Last 5 Weeks [7]. The counters contain data for one
day, one week or five weeks back in time and up to the current time.
The logging will start at the date programmed in par.23-51
Period Start.
In all cases, the period split will refer to operating hours (time where
adjustable frequency drive is powered up).
[0] Hour of Day
[1] Day of Week
[2] Day of Month
[5] * Last 24 Hours
[6] Last 7 Days
[7] Last 5 Weeks
NOTE
The adjustable frequency drive has no back-up of the clock function and the set date/time will reset to default
(2000-01-01 00:00) after a power-down unless a Real Time Clock module with back-up is insta
lled. Consequently, the
logging will be stopped until date/time is readjusted in par.0-70
Date and Time. In par.0-79 Clock Fault, it is possible to
program for a warning in case the clock has not been set properly, e.g.
, after a power-down.
23-51 Period Start
Range: Function:
Applica-
tion de-
pend-
ent*
[Application dependant]
NOTE
When mounting an Analog I/O MCB109 option card, a battery back-up of the date and time is included.
Parameter Description
TR200 Programming Guide 4-201