Once a second, the value of the operating variable selected is registered. If a value has been registered to equal
13%, the counter “10%–<20%” will be updated with the value “1”. If the value stays at 13% for 10s, then “10”
will be added to the counter value.
The contents of counters can be displayed as bars on keypad. Select
Quick Menu
>
Loggings
:
Trending Continued
Bin / Trending Timed Bin / Trending Comparison
.
NOTE
The counters starts counting whenever the adjustable frequency drive is powered up. The power cycle will shortly after
a reset zero the counters. EEProm data are updated once per hour.
23-60 Trend Variable
Option: Function:
Select the desired operating variable to be monitored for trending.
[0] * Power [kW] Power yielded to the motor. Reference for the relative value is the rated
motor power programmed in par.1-20
Motor Power [kW] or par.
1-21
Motor Power [HP]. Actual value can be read in par.16-10 Power
[kW] or par.16-11 Power [hp].
[1] Current [A] Output current to the motor. Reference for the relative value is the rated
motor current programmed in par.1-24
Motor Current. Actual value can
be read in par.16-14
Motor Current.
[2] Frequency [Hz] Output frequency to the motor. Reference for the relative value is the
maximum output frequency programmed in par.4-14
Motor Speed High
Limit [Hz]. Actual value can be read in par.16-13 Frequency.
[3] Motor Speed [RPM] Speed of the motor. Reference for relative value is the maximum motor
speed programmed in par.4-13
Motor Speed High Limit [RPM].
Parameter Description
4-204 TR200 Programming Guide