23-61 Continuous Bin Data
Range: Function:
0 N/A* [0 - 4294967295 N/A] Array with 10 elements ([0]-[9] below parameter number in display).
Press OK and step between elements by means of
and
buttons on
the keypad.
10 counters with the frequency of occurrence for the operating variable
monitored, sorted according to the following intervals:
Counter [0]: 0%–<10%
Counter [1]: 10%–<20%
Counter [2]: 20%–<30%
Counter [3]: 30%–<40%
Counter [4]: 40%–<50%
Counter [5]: 50%–<60%
Counter [6]: 60%–<70%
Counter [7]: 70%–<80%
Counter [8]: 80%–<90%
Counter [9]: 90%–<100% or Max
The above minimum limits for the intervals are the default limits. These
can be changed in par.23-65
Minimum Bin Value.
Starts to count when the adjustable frequency drive is powered up for
the first time. All counters can be reset to 0 in par.23-66
Reset Continuous
Bin Data.
23-62 Timed Bin Data
Range: Function:
0 N/A* [0 - 4294967295 N/A] Array with 10 elements ([0]-[9] below parameter number in display).
Press OK and step between elements by means of
and
buttons on
the keypad.
10 counters with the frequency of occurrence for the operating data
monitored sorted according to the intervals as for par.23-61
Continuous
Bin Data.
Starts to count at the date/time programmed in par.23-63
Timed Period
Start, and stops at the time/date programmed in par.23-64 Timed Period
Stop. All counters can be reset to 0 in par.23-67 Reset Timed Bin Data.
23-63 Timed Period Start
Range: Function:
Applica-
tion de-
pend-
ent*
[Application dependant]
Parameter Description
TR200 Programming Guide 4-205