23-61 Continuous Bin Data
Range: Function:
0 N/A* [0 - 4294967295 N/A] Array with 10 elements ([0]-[9] below parameter number in display).
Press OK and step between elements by means of
Ⴃ
and
Ⴍ
buttons on
the keypad.
10 counters with the frequency of occurrence for the operating variable
monitored, sorted according to the following intervals:
Counter [0]: 0%–<10%
Counter [1]: 10%–<20%
Counter [2]: 20%–<30%
Counter [3]: 30%–<40%
Counter [4]: 40%–<50%
Counter [5]: 50%–<60%
Counter [6]: 60%–<70%
Counter [7]: 70%–<80%
Counter [8]: 80%–<90%
Counter [9]: 90%–<100% or Max
The above minimum limits for the intervals are the default limits. These
can be changed in par.23-65
Minimum Bin Value.
Starts to count when the adjustable frequency drive is powered up for
the first time. All counters can be reset to 0 in par.23-66
Reset Continuous
Bin Data.
23-62 Timed Bin Data
Range: Function:
0 N/A* [0 - 4294967295 N/A] Array with 10 elements ([0]-[9] below parameter number in display).
Press OK and step between elements by means of
Ⴃ
and
Ⴍ
buttons on
the keypad.
10 counters with the frequency of occurrence for the operating data
monitored sorted according to the intervals as for par.23-61
Continuous
Bin Data.
Starts to count at the date/time programmed in par.23-63
Timed Period
Start, and stops at the time/date programmed in par.23-64 Timed Period
Stop. All counters can be reset to 0 in par.23-67 Reset Timed Bin Data.
23-63 Timed Period Start
Range: Function:
Applica-
tion de-
pend-
ent*
[Application dependant]
TR200 Programming Guide 4-205