0-10 Active Set-up
Option: Function:
Select the set-up in which the adjustable frequency drive is to operate.
Use par.0-51
Set-up Copy to copy a set-up to one or all other set-ups. To
avoid conflicting settings of the same parameter within two different set-
ups, link the set-ups together using par.0-12
This Set-up Linked to. Stop
the adjustable frequency drive before switching between set-ups, where
parameters marked ‘not changeable during operation’ have different
values.
Parameters that are ‘not changeable during operation’ are marked
FALSE in the parameter lists in the section Parameter Lists.
[0] Factory setup Cannot be changed. It contains the Trane data set, and can be used as a
data source when returning the other set-ups to a known state.
[1] * Set-up 1
Set-up 1
[1] to
Set-up 4
[4] are the four separate parameter set-ups within
which all parameters can be programmed.
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] Multi setup Is used for remote selection of set-ups using digital inputs and the serial
communication port. This set-up uses the settings from par.0-12
This
Set-up Linked to.
0-11 Programming Set-up
Option: Function:
Select the set-up to be edited (i.e., programmed) during operation; either
the active set-up or one of the inactive set-ups. The set-up number being
edited is displayed in the keypad in (brackets).
[0] Factory setup cannot be edited, but it is useful as a data source to return the other set-
ups to a known state.
[1] Set-up 1
Set-up 1
[1] to
Set-up 4
[4] can be edited freely during operation, inde-
pendently of the active set-up.
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] * Active Set-up (i.e., the set-up in which the adjustable frequency drive is operating) can
also be edited during operation. Editing parameters in the chosen set-up
would normally be done from the keypad but it is also possible from any
of the serial communication ports.
0-12 This Set-up Linked to
Option: Function:
This parameter only needs to be programmed if changing set-ups is re-
quired while the motor is running. It ensures that parameters that are
'not changeable during operation' have the same setting in all relevant
set-ups.
TR200 Programming Guide 4-5