To enable conflict-free changes from one set-up to another while the ad-
justable frequency drive is running, link set-ups containing parameters
that are not changeable during operation. The link will ensure the proper
synchronization of the ‘not changeable during operation’ parameter val-
ues when moving from one set-up to another during operation. ‘Not
changeable during operation’ parameters can be identified by the label
FALSE in the parameter lists in the section
Parameter Lists
.
The par.0-12
This Set-up Linked to feature is used when Multi set-up in
par.0-10
Active Set-up is selected. Multi set-up can be used to move from
one set-up to another during operation (i.e., while the motor is running).
Example:
Use Multi set-up to shift from Set-up 1 to Set-up 2 while the motor is
running. Program parameters in Set-up 1 first, then ensure that Set-up 1
and Set-up 2 are synchronized (or ‘linked’). Synchronization can be per-
formed in two ways:
1. Change the edit set-up to
Set-up 2
[2] in par.0-11 Programming Set-
up and set par.0-12 This Set-up Linked to to
Set-up 1
[1]. This will start
the linking (synchronizing) process.
130BP075.10
OR
2. While still in Set-up 1, using par.0-50
LCP Copy, copy Set-up 1 to Set-
up 2. Then set par.0-12
This Set-up Linked to to
Set-up 2
[2]. This will start
the linking process.
130BP076.10
After the link is complete, par.0-13 Readout: Linked Set-ups will read {1,2}
to indicate that all ‘not changeable during operation’ parameters are now
the same in Set-up 1 and Set-up 2. If there are changes to a ‘not change-
able during operation’ parameter, e.g. par.1-30
Stator Resistance (Rs) in
Set-up 2, they will also be changed automatically in Set-up 1. A switch
between Set-up 1 and Set-up 2 during operation is now possible.
[0] * Not linked