[1662] Analog Input 53 Actual value at input 53 either as a reference or protection value.
[1663] Terminal 54 Switch Set-
ting
Setting of input terminal 54. Current = 0; Voltage = 1.
[1664] Analog Input 54 Actual value at input 54 either as reference or protection value.
[1665] Analog Output 42 [mA] Actual value at output 42 in mA. Use par.6-50
Terminal 42 Output to se-
lect the variable to be represented by output 42.
[1666] Digital Output [bin] Binary value of all digital outputs.
[1667] Pulse Input #29 [Hz] Actual value of the frequency applied at terminal 29 as a pulse input.
[1668] Pulse Input #33 [Hz] Actual value of the frequency applied at terminal 33 as a pulse input.
[1669] Pulse Output #27 [Hz] Actual value of pulses applied to terminal 27 in digital output mode.
[1670] Pulse Output #29 [Hz] Actual value of pulses applied to terminal 29 in digital output mode.
[1671] Relay Output [bin] View the setting of all relays.
[1672] Counter A View the present value of Counter A.
[1673] Counter B View the present value of Counter B.
[1675] Analog In X30/11 Actual value of the signal on input X30/11 (General Purpose I/O Card.
Option)
[1676] Analog In X30/12 Actual value of the signal on input X30/12 (General Purpose I/O Card.
Optional)
[1677] Analog Out X30/8 [mA] Actual value at output X30/8 (General Purpose I/O Card. Optional) Use
Par. 6-60 to select the variable to be shown.
[1680] Fieldbus CTW 1 Control word (CTW) received from the bus master.
[1682] Fieldbus REF 1 Main reference value sent with control word via the serial communica-
tions network, e.g., from the BMS, PLC or other master controller.
[1684] Comm. Option Status Extended serial communication option status word.
[1685] FC Port CTW 1 Control word (CTW) received from the bus master.
[1686] FC Port REF 1 Status word (STW) sent to the bus master.
[1690] Alarm Word One or more alarms in a Hex code (used for serial communications)
[1691] Alarm word 2 One or more alarms in a Hex code (used for serial communications)
[1692] Warning Word One or more warnings in a Hex code (used for serial communications)
[1693] Warning word 2 One or more warnings in a Hex code (used for serial communications)
[1694] Ext. Status Word One or more status conditions in a Hex code (used for serial communi-
cations)
[1695] Ext. Status Word 2 One or more status conditions in a Hex code (used for serial communi-
cations)
[1696] Maintenance Word The bits reflect the status for the programmed preventive maintenance
events in parameter group 23-1*
Parameter Description