[1614] Motor Current Phase current of the motor measured as effective value.
[1615] Frequency [%] Motor frequency, i.e., the output frequency from the adjustable frequen-
cy drive in percent.
[1616] Torque [Nm] Present motor load as a percentage of the rated motor torque.
[1617] Speed [RPM] Motor speed reference. Actual speed will depend on slip compensation
being used (compensation set in par.1-62
Slip Compensation). If not
used, actual speed will be the value read in the display minus motor slip.
[1618] Motor Thermal Thermal load on the motor, calculated by the ETR function. See also pa-
rameter group 1-9* Motor Temperature.
[1622] Torque [%] Shows the actual torque produced, in percentage.
[1626] Power Filtered [kW]
[1627] Power Filtered [hp]
[1630] DC Link Voltage Intermediate circuit voltage in the adjustable frequency drive.
[1632] Brake Energy /s Present braking energy transferred to an external brake resistor.
Stated as an instantaneous value.
[1633] Brake Energy /2 min Braking energy transferred to an external brake resistor. The mean pow-
er is calculated continuously for the most recent 120 seconds.
[1634] Heatsink Temp. Present heatsink temperature of the adjustable frequency drive. The cut-
out limit is 203° ± 41°F [95° ± 5rC]; cutting back in occurs at 158° ± 41°F
[70° ± 5rC].
[1635] Inverter Thermal Percentage load of the inverters
[1636] Inv. Nom. Current Nominal current of the adjustable frequency drive.
[1637] Inv. Max. Current Maximum current of the adjustable frequency drive.
[1638] SL Controller State State of the event executed by the control
[1639] Control Card Temp. Temperature of the control card.
[1650] External Reference Sum of the external reference as a percentage, i.e., the sum of analog/
pulse/bus.
[1652] Feedback [Unit] Reference value from programmed digital input(s).
[1653] Digi Pot Reference View the contribution of the digital potentiometer to the actual reference
Feedback.
[1654] Feedback 1 [Unit] View the value of Feedback 1. See also par. 20-0*.
[1655] Feedback 2 [Unit] View the value of Feedback 2. See also par. 20-0*.
[1656] Feedback 3 [Unit] View the value of Feedback 3. See also par. 20-0*.
[1658] PID Output [%] Returns the Drive Closed-loop PID controller output value in percent.
[1660] Digital Input Displays the status of the digital inputs. Signal low = 0; Signal high = 1.
Regarding order, see par.16-60
Digital Input. Bit 0 is at the extreme right.
[1661] Terminal 53 Switch Set-
ting
Setting of input terminal 53. Current = 0; Voltage = 1.
Parameter Description
TR200 Programming Guide 4-9