[37] Display Text 1 Enables an individual text string to be written, for display in the keypad
or to be read via serial communication.
[38] Display Text 2 Enables an individual text string to be written, for display in the keypad
or to be read via serial communication.
[39] Display Text 3 Enables an individual text string to be written, for display in the keypad
or to be read via serial communication.
[89] Date and Time Readout Displays the current date and time.
[953] Profibus Warning Word Displays Profibus communication warnings.
[1005] Readout Transmit Error
Counter
View the number of CAN control transmission errors since the last pow-
er-up.
[1006] Readout Receive Error
Counter
View the number of CAN control receipt errors since the last power-up.
[1007] Readout Bus Off Counter View the number of Bus Off events since the last power-up.
[1013] Warning Parameter View a DeviceNet-specific warning word. One separate bit is assigned to
every warning.
[1115] LON Warning Word Shows the LON-specific warnings.
[1117] XIF Revision Shows the version of the external interface file of the Neuron C chip on
the LON option.
[1118] LonWorks Revision Shows the software version of the application program of the Neuron C
chip on the LON option.
[1501] Running Hours View the number of running hours of the motor.
[1502] kWh Counter View the line power consumption in kWh.
[1600] Control Word View the control word sent from the adjustable frequency drive via the
serial communication port in hex code.
[1601] Reference [Unit] Total reference (sum of digital/analog/preset/bus/freeze ref./catch up and
slow-down) in selected unit.
[1602] * Reference % Total reference (sum of digital/analog/preset/bus/freeze ref./catch up and
slow-down) in percent.
[1603] Status Word Present status word
[1605] Main Actual Value [%] View the two-byte word sent with the status word to the bus master re-
porting the main actual value.
[1609] Custom Readout View the user-defined readouts as defined in par.0-30
Custom Readout
Unit, par.0-31 Custom Readout Min Value and par.0-32 Custom Readout
Max Value.
[1610] Power [kW] Actual power consumed by the motor in kW.
[1611] Power [hp] Actual power consumed by the motor in HP.
[1612] Motor voltage Voltage supplied to the motor.
[1613] Frequency Motor frequency, i.e., the output frequency from the adjustable frequen-
cy drive in Hz.
Parameter Description
4-8 TR200 Programming Guide