If par.0-61 Access to Main Menu w/o Password is set to
Full access
[0], this parameter will be ignored.
Set the time and date of the internal clock. The internal clock can be used, for example, for timed actions, energy
log, trend analysis, date/time stamps on alarms, logged data and preventive maintenance.
It is possible to program the clock for Daylight Saving Time/summertime, weekly working days/non-working
days including 20 exceptions (holidays, etc.). Although the clock settings can be set via the keypad, they can
also be set along with timed actions and preventative maintenance functions using the MCT10 software tool.
NOTE
The adjustable frequency drive has no backup of the clock function and the set date/time will reset to default (2000-01-01
00:00) after a power-down unless a Real Time Clock module with backup is install
ed. If no module with backup is
installed, it is recommended the clock function is only used if the ad
justable frequency drive is integrated into the BMS
using serial communications, with the BMS maintain
ing synchronization of control equipment clock times. In par.
0-79
Clock Fault, it is possible to program for a warning in case the clock has not been set properly, e.g., after a power-
down.
NOTE
If mounting an Analog I/O MCB 109 option card, a battery backup of the date and time is included.
0-70 Date and Time
Range: Function:
Applica-
tion de-
pend-
ent*
[Application dependant]
0-71 Date Format
Option: Function:
Sets the date format to be used in the keypad.
[0] * YYYY-MM-DD
[1] * DD-MM-YYYY
[2] MM/DD/YYYY
0-72 Time Format
Option: Function:
Sets the time format to be used in the keypad.
[0] * 24 h
[1] 12 h
0-74 DST/Summertime
Option: Function:
Choose how Daylight Saving Time/Summertime should be handled. For
manual DST/Summertime enter the start date and end date in par.
0-76
DST/Summertime Start and par.0-77 DST/Summertime End.
[0] * OFF
[2] Manual
4-20 TR200 Programming Guide