1-23 Motor Frequency
Range: Function:
Applica-
tion de-
pend-
ent*
[20 - 1000 Hz] Select the motor frequency value from the motor nameplate data.For 87
Hz operation with 230/400 V motors, set the nameplate data for 230 V/50
Hz. Adapt par.4-13
Motor Speed High Limit [RPM] and par.3-03 Maxi-
mum Reference to the 87 Hz application.
NOTE: This parameter cannot be adjusted while the motor is running.
1-24 Motor Current
Range: Function:
Applica-
tion de-
pend-
ent*
[Application dependant]
NOTE
This parameter cannot be adjusted while the motor is running.
1-25 Motor Nominal Speed
Range: Function:
Applica-
tion de-
pend-
ent*
[100 - 60000 RPM] Enter the nominal motor speed value from the motor nameplate data.
This data is used for calculating automatic motor compensations.
NOTE
This parameter cannot be changed while the motor is running.
1-28 Motor Rotation Check
Option: Function:
Following installation and connection of the motor, this function allows
the correct motor rotation direction to be verified. Enabling this function
overrides any bus commands or digital inputs, except External Interlock
and Safe Stop (if included).
[0] * OFF
Motor Rotation Check is not active.
[1] Enabled Motor Rotation Check is enabled. Once enabled, display shows:
"Please Note! Motor may run in wrong direction".
Pressing [OK], [Back] or [Cancel] will dismiss the message and display a new message: “Press [Hand on] to start
the motor. Press [Cancel] to abort”. Pressing [Hand on] starts the motor at 5 Hz in forward direction and the
display shows: “Motor is running. Check if motor rotation direction is correct. Press [Off] to stop the motor”.
Pressing [Off] stops the motor and resets par.1-28
Motor Rotation Check. If motor rotation direction is incorrect,
two motor phase cables should be interchanged. IMPORTANT:
CAUTION
Line power must be removed before disconnecting motor phase cables.
Parameter Description
4-24 TR200 Programming Guide