4-51 Warning Current High
Range: Function:
Applica-
tion de-
pend-
ent*
[Application dependant]
4-53 Warning Speed High
Range: Function:
Applica-
tion de-
pend-
ent*
[Application dependant]
NOTE: Any changes in par.4-13
Motor Speed High Limit [RPM] will reset the value in par.4-53 Warning Speed
High to the same value as set in par.4-13 Motor Speed High Limit [RPM].
If a different value is needed in par.4-53
Warning Speed High, it must be set after programming of par.
4-13
Motor Speed High Limit [RPM]!
4-54 Warning Reference Low
Range: Function:
-999999.
999 N/
A*
[Application dependant] Enter the lower reference limit. When the actual reference falls below this
limit, the display indicates Ref Low. The signal outputs can be program-
med to produce a status signal on terminal 27 or 29 and on relay output
01 or 02.
4-55 Warning Reference High
Range: Function:
999999.
999 N/
A*
[Application dependant] Enter the upper reference limit. When the actual reference exceeds this
limit, the display reads Ref High. The signal outputs can be programmed
to produce a status signal on terminal 27 or 29 and on relay output 01 or
02.
4-56 Warning Feedback Low
Range: Function:
-999999.
999
Proc-
essCtrlU-
nit*
[Application dependant] Enter the lower feedback limit. When the feedback falls below this limit,
the display reads Feedb Low. The signal outputs can be programmed to
produce a status signal on terminal 27 or 29 and on relay output 01 or
02.
4-57 Warning Feedback High
Range: Function:
999999.
999
Proc-
essCtrlU-
nit*
[Application dependant] Enter the upper feedback limit. When the feedback exceeds this limit, the
display reads Feedb High. The signal outputs can be programmed to
produce a status signal on terminal 27 or 29 and on relay output 01 or
02.
TR200 Programming Guide 4-49