drive via a terminal programmed for Coasting inverse [2] or Coast and
reset, inverse [3].
[21] Speed up For digital control of the up/down speed is desired (motor potentiome-
ter). Activate this function by selecting either Freeze reference or Freeze
output. When Speed up is activated for less than 400 msec., the resulting
reference will be increased by 0.1%. If Speed up is activated for more
than 400 msec., the resulting reference will ramp according to Ramp 1
in par.3-41
Ramp 1 Ramp-up Time.
[22] Slow Same as Speed up [21].
[23] Set-up select bit 0 Selects one of the four set-ups. Set par. 0-10 to Multi Set-up.
[24] Set-up select bit 1 Same as Set-up select bit 0 [23].
(Default Digital input 32)
[32] Pulse input Select Pulse input when using a pulse sequence as either reference or
feedback. Scaling is done in par. group 5-5*.
[34] Ramp bit 0 Select which ramp to use. Logic “0” will select ramp 1 while logic “1”
will select ramp 2.
[36] Mains failure inverse Select to activate function selected in par.14-10
Mains Failure. Line fail-
ure is active in the Logic “0” situation.
[37] Fire mode A signal applied will put the adjustable frequency drive into fire mode
and all other commands will be disregarded. See 24-0*
Fire Mode
.
[52] Run Permissive The input terminal, for which the Run permissive has been programmed
must be logic “1” before a start command can be accepted. Run permis-
sive has a logic ‘AND’ function related to the terminal which is program-
med for
START
[8],
Jog
[14] or
Freeze Output
[20], which means that in
order to start running the motor, both conditions must be fulfilled. If Run
Permissive is programmed on multiple terminals, Run permissive needs
only be logic ‘1’ on one of the terminals for the function to be carried out.
The digital output signal for Run Request (
Start
[8],
Jog
[14] or
Freeze out-
put
[20]) programmed in par. 5-3*, or par. 5-4*, will not be affected by
Run Permissive.
NOTE: If no Run Permissive signal is applied but either Run, Jog or Freeze
commands is activated, the status line in the display will show either Run
Requested, Jog Requested or Freeze Requested.
[53] Hand start A signal applied will put the adjustable frequency drive into hand mode
as if button
Hand On
on the keypad has been pressed and a normal stop
command will be overridden. If disconnecting the signal, the motor will
stop. To make any other start commands valid, another digital input must
be assigned to
Auto-Start
and a signal applied to this. The
Hand On
and
Auto On
buttons on the keypad has no impact. The
Off
button on the
keypad will override
Hand Start
and
Auto-Start
. Press either the
Hand On
or
Auto On
button to make
Hand Start
and
Auto-Start
active again. If no
signal on neither
Hand Start
nor
Auto-Start
, the motor will stop regardless
of any normal Start command applied. If signal applied to both
Hand
Start
and
Auto-Start
, the function will be
Auto-Start
. If pressing the
Off
button on the keypad, the motor will stop regardless of signals on
Hand
Start
and
Auto-Start
.
[54] Auto start A signal applied will put the adjustable frequency drive into auto mode
as if the keypad button
Auto On
has been pressed. See also
Hand Start
[53]
Parameter Description
TR200 Programming Guide 4-59