EasyManua.ls Logo

Trane TR200 - How to Test Motor and Direction of Rotation

Trane TR200
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
Function Setting
5-10 Terminal 18
Digital Input
[8] Start
5-11 Terminal 19
Digital Input
[10]
Reversing*
5-12 Terminal 27
Digital Input
[0]
No
operation
5-1
4 Terminal 32
Digital Input
[16]
Pr
eset
ref bit 0
5-15 Terminal 33
Digital Input
[17] Preset
ref bit 1
3-10 Preset
Reference
Preset ref. 0
Preset ref. 1
Preset ref. 2
Preset ref. 3
25%
50%
75%
100%
*=Default Value
Notes/comments:
Table 6.7 Start/Stop with Reversing and 4 Preset Speeds
Parameters
Function Setting
5-11 Terminal 19
Digital Input
[1] Reset
*=Default Value
Notes/comments:
Table 6.8 External Alarm Reset
Parameters
Function Setting
6-10 Terminal 53
Low Voltage 0.07 V*
6-11 Terminal 53
High Voltage
10 V*
6-14 Terminal 53
Low Ref./Feedb.
Value
0 RPM
6-15 Terminal 53
High Ref./Feedb.
Value
1500 RPM
*=Default Value
Notes/comments:
Table 6.9 Speed Reference (using a Manual Potentiometer)
Parameters
Function Setting
5-10 Terminal 18
Digital Input
[8]
St
art*
5-12 Terminal 27
Digital Input
[19]
Freeze
Reference
5-13 Terminal 29
Digital Input
[21]
Spe
ed
Up
5-14 Terminal 32
Digital Input
[22] Speed
Down
*=Default Value
Notes/comments:
Table 6.10 Speed Up/Down
TR200 D-Frame Operating Instructions Application Examples
BAS-SVX54B-EN
51

Table of Contents

Other manuals for Trane TR200

Related product manuals