S t a r t ( 1 8 )
F r e e z e r e f ( 2 7 )
S p e e d u p ( 2 9 )
S p e e d d o w n ( 3 2 )
S p e e d
R e f e r e n c e
130BB840.10
Illustration 6.3 Speed Up/Down
Parameters
Function Setting
8-30 Protocol FC*
8-31 Address 1*
8-32 Baud Rate 9600*
*=Default Value
Notes/comments:
Select protocol, address and
baud rate in the above
mentioned parameters.
Table 6.11 RS-485 Network Connection
Parameters
Function Setting
1-90 Motor
Thermal
Protection
[2]
Thermistor
trip
1-93 Thermistor
Source
[1]
Analog
input 53
*=Default Value
Notes/comments:
If only a warning is desired,
1-90 Motor Thermal Protection
should be set to [1] Thermistor
warning.
Table 6.12 Motor Thermistor
Application Examples TR200 D-Frame Operating Instructions
52
BAS-SVX54B-EN