Parameters
Function Setting
4-30 Motor
Feedback Loss
Function [1]
Warning
4-31 Motor
Feedback Speed
Error
100 RPM
4-32 Motor
Feedback Loss
Timeout
5 s
7-00 Speed PID
Feedback Source
[2] MCB 102
17-11 Resolution
(PPR)
1024*
13-00 SL
Controller Mode
[1] On
13-01 Start
Event
[19] Warning
13-02 Stop
Event
[44] Reset
key
13-10 Comparat
or Operand
[21]
Warning
no.
13-11 Comparat
or Operator
[1] ≈*
13-12 Comparat
or Value
90
13-51 SL
Controller Event
[22]
Comparator 0
13-52 SL
Controller Action
[32] Set
digital out A
low
5-40 Function
Relay
[80]
SL digital
output A
*=Default Value
Notes/comments:
If the limit in the feedback
monitor is exceeded, Warning
90 will be issued. The SLC
monitors Warning 90 and in the
case that Warning 90 becomes
TRUE then Relay 1 is triggered.
External equipment may then
indicate that service may be
required. If the feedback error
goes below the limit again
within 5 s then the frequency
converter continues and the
warning disappears. But Relay 1
will still be triggered until
[Reset] on the LCP.
Table 6.13 Using SLC to Set a Relay
Illustration 6.4 Mechanical Brake Control
TR200 D-Frame Operating Instructions Application Examples
BAS-SVX54B-EN
53