Chapter 5 Network variable bindings
18 CNT-SVX09B-EN
nvoCurrent3 SNVT_amp_mil Universal input 3 sta-
tus output
Indicates the value of universal input 3 if it is
configured as 0–20 mA.
If universal input 3 is not configured as 0–20
mA, this output is -3276.8.
nvoCurrent4 SNVT_amp_mil Universal input 4 sta-
tus output
Indicates the value of universal input 4 if it is
configured as 0–20 mA.
If universal input 4 is not configured as 0–20
mA, this output is -3276.8.
nvoVolts1 SNVT_volt Universal input 1 sta-
tus output
Indicates the value of universal input 1 if it is
configured as 0–10 Vdc.
If universal input 1 is not configured as 0–10
Vdc, this output is -3276.8.
nvoVolts2 SNVT_volt Universal input 2 sta-
tus output
Indicates the value of universal input 2 if it is
configured as 0–10 Vdc.
If universal input 2 is not configured as 0–10
Vdc, this output is -3276.8.
nvoVolts3 SNVT_volt Universal input 3 sta-
tus output
Indicates the value of universal input 3 if it is
configured as 0–10 Vdc.
If universal input 3 is not configured as 0–10
Vdc, this output is -3276.8.
nvoVolts4 SNVT_volt Universal input 4 sta-
tus output
Indicates the value of universal input 4 if it is
configured as 0–10 Vdc.
If universal input 4 is not configured as 0–10
Vdc, this output is -3276.8.
nvoBOP1Status SNVT_switch Binary output 1
status output
Indicates the value of binary output 1.
nvoBOP2Status SNVT_switch Binary output 2
status output
Indicates the value of binary output 2.
nvoBOP3Status SNVT_switch Binary output 3
status output
Indicates the value of binary output 3.
nvoBOP4Status SNVT_switch Binary output 4
status output
Indicates the value of binary output 4.
Table 2. Tracer MP503 network variable outputs
Variable name Data type Description